Asynchronous motor(Induction Motor) Starters | Comparison of induction motor starters

As the name indicates, starters are used to start or stop a motor. It consists of an electromechanical switch and protection devices (overload and/or short-circuit protection).

Why should we need a starter?

An induction motor draws 5-10 times its rated current during start. In order to reduce the starting current, we need a starter. If we don’t use a starter, inrush currents may heat up the motor winding and the life of motor may reduce.

Comparison of three phase induction motor starters

Method

Starting current

Starting Torque

Pros

Cons

Direct-on-Line (DOL)
5-10 times the full load current
5-10 times the full load torque
Economical and Higher starting torque.
High in-rush current
Star-Delta Starter
2-3 times the full load current
2-3 times the full load torque
Inrush current can be reduced to one-third when compared to DOL.
Starting torque will reduce
Auto-transformer
2-3 times the full load current
2-3 times the full load torque
Inrush current can be reduced to one-third when compared to DOL.
Starting torque will reduce
Soft starter
3-5 times the full load current
1.5-2.5 times the full load torque
Inrush current can be reduced. Starting torque can be controlled.
Starting torque will be less
Variable Speed drive
1.1-1.5 times full load current
1.5-2.5 times the full load torque
Speed and torque control, communication and Energy saving.
Higher cost